4. Cross reference for [Ontology Name] classes, properties and dataproperties

This section provides details for each class and property defined by [Ontology Name].

Classes

actuatorc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Actuator

has super-classes
manual override dp only boolean
fail position dp only string

air to air heat recoveryc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#AirToAirHeatRecovery

has super-classes
has defrost dp only boolean
secondary air flow rate range dp only real real range c
primary air flow rate range dp only real real range c
operational temperature range dp only real real range c
heat transfer type enum dp only string

audio visual appliancec back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#AudioVisualAppliance

has super-classes
audio volume dp only float
media source dp only string

boilerc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Boiler

has super-classes
nominal part load ratio dp only real real range c
water inlet temperature range dp only real real range c
operating mode dp only string
is water storage heater dp only boolean
water storage capacity dp only float
energy source dp only string
nominal energy consumption dp only float
outlet temperature range dp only real real range c
pressure rating dp only float
heat transfer surface area dp only float

burnerc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Burner

has super-classes
energy source dp only string

chillerc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Chiller

has super-classes
nominal heat rejection rate dp only float
nominal condensing temperature dp only float
nominal efficiency dp only float
nominal power consumption dp only float
nominal capacity dp only float
nominal evaporating temmperature dp only float

coilc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Coil

has super-classes
placement type dp only string
nominal latent capacity dp only float
nominal ua dp only float
nominal sensible capacity dp only float
operational temperature range dp only real real range c
air flow rate range op only real real range c

compressorc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Compressor

has super-classes
compressor speed dp only float
ideal shaft power dp only float
minimun part load ratio dp only float
power source dp only string
refrigerant class dp only string
nominal capacity dp only float
ideal capacity dp only float
impeller diameter dp only float
maximum part load ratio dp only float
has hot gas bypass dp only boolean

condenserc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Condenser

has super-classes
nominal heat transfer coefficient dp only float
internal surface area dp only float
internal water volume dp only float
internal refrigerant volume dp only float
external surface area dp only float
refrigerant class dp only string
nominal heat transfer area dp only float

cooled beamc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#CooledBeam

has super-classes
is free hanging dp only boolean
integrated lighting type dp only string
nominal return water temperature heating dp only float
nominal sorrounding temperature heating dp only float
pipe connection enum dp only string
nominal supply water temperature heating dp only float
coil width dp only float
nominal supply water temperature cooling dp only float
nominal water flow heating dp only float
nominal heating capacity dp only float
water pressure range dp only real real range c
coil length dp only float
water flow control system type dp only string
nominal sorrounding temperature cooling dp only float
nominal return water temperature cooling dp only float
finish color dp only string
nominal cooling capacity dp only float
nominal water flow cooling dp only float
nominal sorrounding humidity cooling dp only float

cooling towerc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#CoolingTower

has super-classes
number of cells dp only integer
spray type dp only string
lift elevation difference dp only float
ambient design dry bulb temperature dp only float
basin reserve volume dp only float
circuit type dp only string
control strategy dp only string
flow arrangement dp only string
ambient design wet bulb temperature dp only float
water requirement dp only float
operation temperature range dp only float
nominal capcity dp only float
capacity control dp only string

damperc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Damper

has super-classes
number of blades dp only integer
temperature rating dp only float
leakage fully closed dp only float
frame thickness dp only float
close off rating dp only float
open pressure drop dp only float
operation dp only string
blade action dp only string
blade thickness dp only float
frame depth dp only float
temperature range dp only real real range c
blade edge dp only string
maximum air flow rate dp only float
frame type dp only string
nominal air flow rate dp only float
orientation dp only string
face area dp only float
maximum working pressure dp only float
blade shape dp only string

duct silencerc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#DuctSilencer

has super-classes
working pressure range dp only real real range c
has exterior insulation dp only boolean
air flow rate range op only real real range c
weight dp only float
hydraulic diameter dp only float
temperature range dp only real real range c
length dp only float

electric flow storage devicec back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#ElectricFlowStorageDevice

has super-classes
nominal frequency dp only float
nominal supply voltage dp only float
nominal supply voltage offset dp only real real range c

electric generatorc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#ElectricGenerator

has super-classes
maximum power output dp only float
electric generator efficiency dp only float
start current factor dp only float

electric motorc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#ElectricMotor

has super-classes
starting time dp only float
has part winding dp only boolean
locked rotor current dp only float
te time dp only float
motor enclosure type dp only string
frame size dp only string
electric motor efficiency dp only float
start current factor dp only float
maximum power output dp only float
is guarded dp only boolean

enginec back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Engine

has super-classes
energy source dp only string

evaporative coolerc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#EvaporativeCooler

has super-classes
operational temperature range dp only real real range c
water requirement dp only float
flow arrangement dp only string
heat exchange area dp only float

evaporatorc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Evaporator

has super-classes
nominal heat transfer coefficient dp only float
external surface area dp only float
nominal heat transfer area dp only float
evaporation coolant dp only string
internal water volume dp only float
internal refrigerant volume dp only float
refrigerant class dp only string
evaporation medium type dp only string
internal surface area dp only float

fanc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Fan

has super-classes
nominal power rate dp only float
operational riterial dp only float
nominal total pressure dp only float
motor drive type dp only string
nominal static pressure dp only float
operation temperature range dp only real real range c
nominal rotation speed dp only float
nominal air flow rate dp only float
capacity control type dp only string

filterc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Filter

has super-classes
nominal media surface velocity dp only float
initial resistance dp only float
nominal pressure drop dp only float
operation temperature range dp only real real range c
nominal filter face velocity dp only float
flow rate range dp only real real range c
nominal flow rate dp only float
final resistance dp only float
nominal particle geometric standard deviation dp only float
nominal particle geometric mean diameter dp only float
weight dp only float

flow meterc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#FlowMeter

has super-classes
read out type dp only string
remote reading dp only boolean

heat exchangerc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#HeatExchanger

has super-classes
arrangement dp only string

humidifierc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Humidifier

has super-classes
nominal moisture gain dp only float
water requirement dp only float
nominal air flow rate dp only float
application dp only string
internal control dp only string
weight dp only float

interceptorc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Interceptor

has super-classes
nominal body length dp only float
nominal body depth dp only float
inlet connection size dp only float
ventilating pipe size dp only float
cover width dp only float
cover length dp only float
nominal body width dp only float
outlet connection size dp only float

lampc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Lamp

has super-classes
spectrum dp only real real range c
lamp compensation type dp only string
color rendering index dp only integer
color appearance dp only string
color tempeature dp only float
lamp ballast type dp only string
lamp maintenance factor dp only float
light emitter nominal power dp only float
contributed luminous flux dp only float

outletc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Outlet

has super-classes
is pluggable outlet dp only boolean
number os sockets dp only integer

protective device tripping unitc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#ProtectiveDeviceTrippingUnit

has super-classes
limiting terminal size dp only float
standard dp only string

pumpc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Pump

has super-classes
flow resistance range dp only real real range c
nomminal rotation speed dp only float
net positive suction head dp only float
temperature range dp only real real range c
connection size dp only float
flow rate range dp only real real range c

shading devicec back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#ShadingDevice

has super-classes
solar transmittance dp only float
shading device type dp only string
solar reflectance dp only float
is external dp only boolean
roughness dp only string
mechanical operated dp only boolean
thermal transmittance dp only float
visible light transmittance dp only float
visible light reflectance dp only float

space heaterc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#SpaceHeater

has super-classes
temperature classification dp only string
thermal efficiency dp only float
body mass dp only float
output capacity dp only float
number of sections dp only integer
number of panels dp only integer
thermal mass heat capacity dp only float
placement type dp only string
heat transfer medium dp only string
energy source dp only string
heat transfer dimension dp only string

switching devicec back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#SwitchingDevice

has super-classes
is illuminated dp only boolean
legend dp only string
number of gangs dp only integer
switch function dp only string
has lock dp only boolean

tankc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Tank

has super-classes
first curvature radius dp only float
number of sections dp only integer
nominal capacity dp only float
storage type dp only string
second curvature radius dp only float
access type dp only string
pattern type dp only string
nominal depth dp only float
end shape type dp only string
effective capacity dp only float
nominal length or diameter dp only float
nominal width or diameter dp only float
operating wight dp only float

transformerc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Transformer

has super-classes
secondary current type dp only string
is neutral primary terminal available dp only boolean
is neutral secondary terminal available dp only boolean
primary frequency dp only float
secondary current dp only float
secondary apparent power dp only float
imaginary impedance ratio dp only float
primary voltage dp only float
primary apparent power dp only float
secondary frequency dp only float
secondary voltage dp only float
real impedance ratio dp only float
primary current dp only float
maximum apparent power dp only float
transformer vector group dp only string
short circuit voltage op only complex number c

transport elementc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#TransportElement

has super-classes
fire exit dp only boolean
capacity people dp only positive integer
capacity weight dp only float

tube bundlec back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#TubeBundle

has super-classes
nominal diameter dp only float
volumen dp only float
outside diameter dp only float
inside diameter dp only float
has turbulator dp only boolean
number of circuits dp only integer
in line row spacing dp only float
vertical spacing dp only float
length dp only float
fouling factor dp only float
number of rows dp only integer
staggered row spacing dp only float
thermal conductivity dp only float
horizontal spacing dp only float

valvec back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#Valve

has super-classes
flow coefficient dp only float
close off rating dp only float
size dp only float
working pressure dp only float
test pressure dp only float
valve mechanism dp only string
valve operation dp only string
valve pattern dp only string

vibration isolatorc back to ToC or Class ToC

IRI: http://saref.linkeddata.es/def/bldg#VibrationIsolator

has super-classes
maximum supported weight dp only float
height dp only float
vibration transmissibility dp only float
isolator static deflection dp only float
isolator compressibility dp only float

Object Properties

air flow rate rangeop back to ToC or Object Property ToC

IRI: http://saref.linkeddata.es/def/bldg#airFlowRateRange

Possible range of airflow that can be delivered. For cases where there is no airflow across the coil (e.g. electric coil in a floor slab), then the value is zero. Usually measured in m3/s.
has range
real real range c
is also defined as
data property

short circuit voltageop back to ToC or Object Property ToC

IRI: http://saref.linkeddata.es/def/bldg#shortCircuitVoltage

A complex number that specifies the real and imaginary parts of the short-circuit voltage at rated current of a transformer given in %.
has range
complex number c
is also defined as
data property

Data Properties

access typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#accessType

Defines the types of access (or cover) to a tank that may be specified. Note that covers are generally specified for rectangular tanks. For cylindrical tanks, access will normally be via a manhole.
has range
string

air flow rate rangeop back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#airFlowRateRange

Possible range of airflow that can be delivered. For cases where there is no airflow across the coil (e.g. electric coil in a floor slab), then the value is zero. Usually measured in m3/s.
is also defined as
object property

ambient design dry bulb temperaturedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#ambientDesignDryBulbTemperature

Ambient design dry bulb temperature used for selecting the cooling tower. Usually measured in degrees Kelvin (K).
has range
float

ambient design wet bulb temperaturedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#ambientDesignWetBulbTemperature

Ambient design wet bulb temperature used for selecting the cooling tower. Usually measured in degrees Kelvin (K).
has range
float

applicationdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#application

Humidifier application. Fixed: Humidifier installed in a ducted flow distribution system. Portable: Humidifier is not installed in a ducted flow distribution system.
has range
string

arrangementdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#arrangement

Defines the basic flow arrangements for the heat exchanger: COUNTERFLOW: Counterflow heat exchanger arrangement. CROSSFLOW: Crossflow heat exchanger arrangement. PARALLELFLOW: Parallel flow heat exchanger arrangement. MULTIPASS: Multipass flow heat exchanger arrangement. OTHER: Other type of heat exchanger flow arrangement not defined above.
has range
string

audio volumedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#audioVolume

Indicates discrete audio volume levels and corresponding sound power offsets, if applicable. Missing values may be interpolated. Measured in watts.
has range
float

basin reserve volumedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#basinReserveVolume

Volume between operating and overflow levels in cooling tower basin. Usually measured in cubic metre (m3).
has range
float

blade actiondp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#bladeAction

Blade action.
has range
string

blade edgedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#bladeEdge

Blade edge.
has range
string

blade shapedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#bladeShape

Blade shape. Flat means triple V-groove.
has range
string

blade thicknessdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#bladeThickness

The thickness of the damper blade. Usually measured in millimeters (mm).
has range
float

body massdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#bodyMass

Overall body mass of the heater. Usually measured in kilograms (kg) or grams (g).
has range
float

capacity controldp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#capacityControl

FanCycling: Fan is cycled on and off to control duty. TwoSpeedFan: Fan is switched between low and high speed to control duty. VariableSpeedFan: Fan speed is varied to control duty. DampersControl: Dampers modulate the air flow to control duty. BypassValveControl: Bypass valve modulates the water flow to control duty. MultipleSeriesPumps: Turn on/off multiple series pump to control duty. TwoSpeedPump: Switch between high/low pump speed to control duty. VariableSpeedPump: vary pump speed to control duty.
has range
string

capacity control typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#capacityControlType

InletVane: Control by adjusting inlet vane. VariableSpeedDrive: Control by variable speed drive. BladePitchAngle: Control by adjusting blade pitch angle. TwoSpeed: Control by switch between high and low speed. DischargeDamper: Control by modulating discharge damper.
has range
string

capacity peopledp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#capacityPeople

capacity of the transportation element measured in numbers of person.
has range
positive integer

capacity weightdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#capacityWeight

Capacity of the transport element measured by weight. Usually measured in kilograms (kg) or grams (g).
has range
float

circuit typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#circuitType

OpenCircuit: Exposes water directly to the cooling atmosphere. CloseCircuit: The fluid is separated from the atmosphere by a heat exchanger. Wet: The air stream or the heat exchange surface is evaporatively cooled. Dry: No evaporation into the air stream. DryWet: A combination of a dry tower and a wet tower.
has range
string

close off ratingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#closeOffRating

Close off rating. Usually measured in Pascals (Pa, N/m2).
has range
float

coil lengthdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#coilLength

Length of coil. Usually measured in millimeters (mm).
has range
float

coil widthdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#coilWidth

Width of coil. Usually measured in millimeters (mm
has range
float

color appearancedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#colorAppearance

In both the DIN and CIE standards, artificial light sources are classified in terms of their color appearance. To the human eye they all appear to be white the difference can only be detected by direct comparison. Visual performance is not directly affected by differences in color appearance.
has range
string

color rendering indexdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#colorRenderingIndex

The CRI indicates how well a light source renders eight standard colors compared to perfect reference lamp with the same color temperature. The CRI scale ranges from 1 to 100, with 100 representing perfect rendering properties.
has range
integer

color tempeaturedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#colorTempeature

The color temperature of any source of radiation is defined as the temperature (in Kelvin) of a black-body or Planckian radiator whose radiation has the same chromaticity as the source of radiation. Often the values are only approximate color temperatures as the black-body radiator cannot emit radiation of every chromaticity value. The color temperatures of the commonest artificial light sources range from less than 3000K (warm white) to 4000K (intermediate) and over 5000K (daylight). Usually measured in degrees Kelvin (K).
has range
float

compressor speeddp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#compressorSpeed

Compressor speed. Usually measured in cycles/s.
has range
float

connection sizedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#connectionSize

The connection size of the to and from the pump. Usually measured in millimeters (mm).
has range
float

contributed luminous fluxdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#contributedLuminousFlux

Luminous flux is a photometric measure of radiant flux, i.e. the volume of light emitted from a light source. Luminous flux is measured either for the interior as a whole or for a part of the interior (partial luminous flux for a solid angle). All other photometric parameters are derivatives of luminous flux. Luminous flux is measured in lumens (lm). The luminous flux is given as a nominal value for each lamp. Usually measured in Lumen (lm, Candela Steradian).
has range
float

control strategydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#controlStrategy

FixedExitingWaterTemp: The capacity is controlled to maintain a fixed exiting water temperature. WetBulbTempReset: The set-point is reset based on the wet-bulb temperature.
has range
string

cover lengthdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#coverLength

The length measured along the x-axis in the local coordinate system or the radius (in the case of a circular shape in plan) of the cover of the oil interceptor. Usually measured in millimeters (mm).
has range
float

cover widthdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#coverWidth

The length measured along the x-axis in the local coordinate system of the cover of the oil interceptor. Usually measured in millimeters (mm).
has range
float

effective capacitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#effectiveCapacity

The total effective or actual volumetric capacity of the tank. Usually measured in cubic metre (m3).B3
has range
float

electric generator efficiencydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#electricGeneratorEfficiency

the ratio of output capacity to intake capacity.
has range
float

electric motor efficiencydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#electricMotorEfficiency

The ratio of output capacity to intake capacity.
has range
float

end shape typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#endShapeType

Defines the types of end shapes that can be used for preformed tanks. The convention for reading these enumerated values is that for a vertical cylinder, the first value is the base and the second is the top for a horizontal cylinder, the order of reading should be left to right. For a speherical tank, the value UNSET should be used.B5
has range
string

energy sourcedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#energySource

Enumeration defining the energy source or fuel combusted to generate heat if applicable. Note: hydronic heaters shall use UNSET, dual-use hydronic/electric heaters shall use ELECTRICITY.
has range
string

evaporation coolantdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#evaporationCoolant

The fluid used for the coolant in the evaporator.
has range
string

evaporation medium typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#evaporationMediumType

ColdLiquid: Evaporator is using liquid type of fluid to exchange heat with refrigerant. ColdAir: Evaporator is using air to exchange heat with refrigerant.
has range
string

external surface areadp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#externalSurfaceArea

External surface area (both primary and secondary area). Usually measured in square metre (m2).
has range
float

face areadp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#faceArea

Face area open to the airstream. Usually measured in square metre (m2).
has range
float

fail positiondp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#failPosition

Specifies the required fail-safe position of the actuator.
has range
string

final resistancedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#finalResistance

Filter fluid resistance when replacement is required (i.e., Pressure drop at the maximum air flowrate across the filter when the filter needs replacement per ASHRAE Standard 52.1). Usually measured in Pascals (Pa, N/m2).
has range
float

finish colordp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#finishColor

Finish color for cooled beam.
has range
string

fire exitdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#fireExit

Indication whether this object is designed to serve as an exit in the case of fire (TRUE) or not (FALSE). Here whether the transport element (in case of e.g., a lift) is designed to serve as a fire exit, e.g., for fire escape purposes.
has range
boolean

first curvature radiusdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#firstCurvatureRadius

FirstCurvatureRadius should be defined as the base or left side radius of curvature value. Usually measured in millimeters (mm).
has range
float

flow arrangementdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#flowArrangement

CounterFlow: Air and water flow enter in different directions. CrossFlow: Air and water flow are perpendicular. ParallelFlow: air and water flow enter in same directions.
has range
string

flow coefficientdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#flowCoefficient

Flow coefficient (the quantity of fluid that passes through a fully open valve at unit pressure drop), typically expressed as the Kv or Cv value for the valve.
has range
float

flow rate rangedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#flowRateRange

Allowable range of volume of fluid being pumped against the resistance specified. Usually measured in kg/s.
has range
real real range c

flow resistance rangedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#flowResistanceRange

Allowable range of frictional resistance against which the fluid is being pumped. Usually measured in Pascals (Pa, N/m2).
has range
real real range c

fouling factordp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#foulingFactor

Fouling factor of the tubes in the tube bundle. Usually measured in m2 Kelvin/Watt.
has range
float

frame depthdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#frameDepth

The length (or depth) of the damper frame. Usually measured in millimeters (mm).
has range
float

frame sizedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#frameSize

Designation of the frame size according to the named range of frame sizes designated at the place of use or according to a given standard.
has range
string

frame thicknessdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#frameThickness

The thickness of the damper frame material. Usually measured in millimeters (mm).
has range
float

frame typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#frameType

The type of frame used by the damper (e.g., Standard, Single Flange, Single Reversed Flange, Double Flange, etc.).
has range
string

has defrostdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#hasDefrost

has the heat exchanger has defrost function or not.
has range
boolean

has exterior insulationdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#hasExteriorInsulation

TRUE if the silencer has exterior insulation. FALSE if it does not.
has range
boolean

has hot gas bypassdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#hasHotGasBypass

Whether or not hot gas bypass is provided for the compressor. TRUE = Yes, FALSE = No.
has range
boolean

has lockdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#hasLock

Indication of whether a switching device has a key operated lock (=TRUE) or not (= FALSE).
has range
boolean

has part windingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#hasPartWinding

Indication of whether the motor is single speed, i.e. has a single winding (= FALSE) or multi-speed i.e.has part winding (= TRUE) .
has range
boolean

has turbulatordp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#hasTurbulator

TRUE if the tube has a turbulator, FALSE if it does not.
has range
boolean

heat exchange areadp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#heatExchangeArea

Heat exchange area. Usually measured in square metre (m2).
has range
float

heat transfer dimensiondp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#heatTransferDimension

Indicates how heat is transmitted according to the shape of the space heater.
has range
string

heat transfer mediumdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#heatTransferMedium

Enumeration defining the heat transfer medium if applicable.
has range
string

heat transfer surface areadp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#heatTransferSurfaceArea

Total heat transfer area of the vessel. Usually measured in square metre (m2).
has range
float

heat transfer type enumdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#heatTransferTypeEnum

Type of heat transfer between the two air streams.
has range
string

heightdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#height

Height of the vibration isolator before tha application of load. Usually measured in millimeters (mm).
has range
float

horizontal spacingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#horizontalSpacing

Horizontal spacing between tubes in the tube bundle. Usually measured in millimeters (mm).
has range
float

hydraulic diameterdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#hydraulicDiameter

Hydraulic diameter. Usually measured in millimeters (mm).
has range
float

ideal capacitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#idealCapacity

Compressor capacity under ideal conditions. Usually measured in Watts (W, J/s).
has range
float

ideal shaft powerdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#idealShaftPower

Compressor shaft power under ideal conditions. Usually measured in Watts (W, J/s).
has range
float

imaginary impedance ratiodp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#imaginaryImpedanceRatio

The ratio between the imaginary part of the zero sequence impedance and the imaginary part of the positive impedance (i.e. imaginary part of the short-circuit voltage) of the transformer. Used for three-phase transformer which includes a N-conductor.
has range
float

impeller diameterdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#impellerDiameter

Diameter of compressor impeller - used to scale performance of geometrically similar compressors. Usually measured in millimeters (mm).
has range
float

in line row spacingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#inLineRowSpacing

In-line tube row spacing. Usually measured in millimeters (mm).
has range
float

initial resistancedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#initialResistance

Initial new filter fluid resistance (i.e., pressure drop at the maximum air flowrate across the filter when the filter is new per ASHRAE Standard 52.1). Usually measured in Pascals (Pa, N/m2).
has range
float

inlet connection sizedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#inletConnectionSize

Size of the inlet connection. Usually measured in millimeters (mm).
has range
float

inside diameterdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#insideDiameter

Actual inner diameter of the tube in the tube bundle. Usually measured in millimeters (mm).
has range
float

integrated lighting typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#integratedLightingType

Integrated lighting in cooled beam.
has range
string

internal controldp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#internalControl

Internal modulation control.
has range
string

internal refrigerant volumedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#internalRefrigerantVolume

Internal volume of condenser (refrigerant side). Usually measured in cubic metre (m3).
has range
float

internal surface areadp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#internalSurfaceArea

Internal surface area. Usually measured in square metre (m2).
has range
float

internal water volumedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#internalWaterVolume

Internal volume of condenser (water side). Usually measured in cubic metre (m3).
has range
float

is externaldp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#isExternal

Indication whether the element is designed for use in the exterior (TRUE) or not (FALSE). If (TRUE) it is an external element and faces the outside of the building.
has range
boolean

is free hangingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#isFreeHanging

Is it free hanging type (not mounted in a false ceiling)?
has range
boolean

is guardeddp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#isGuarded

Indication of whether the motor enclosure is guarded (= TRUE) or not (= FALSE).
has range
boolean

is illuminateddp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#isIlluminated

An indication of whether there is an illuminated indicator to show that the switch is on (=TRUE) or not (= FALSE).
has range
boolean

is neutral primary terminal availabledp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#isNeutralPrimaryTerminalAvailable

An indication of whether the neutral point of the primary winding is available as a terminal (=TRUE) or not (= FALSE).
has range
boolean

is neutral secondary terminal availabledp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#isNeutralSecondaryTerminalAvailable

An indication of whether the neutral point of the secondary winding is available as a terminal (=TRUE) or not (= FALSE).
has range
boolean

is pluggable outletdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#isPluggableOutlet

Indication of whether the outlet accepts a loose plug connection (= TRUE) or whether it is directly connected (= FALSE) or whether the form of connection has not yet been determined (= UNKNOWN).
has range
boolean

is water storage heaterdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#isWaterStorageHeater

This is used to identify if the boiler has storage capacity (TRUE). If FALSE, then there is no storage capacity built into the boiler, such as an instantaneous hot water heater.
has range
boolean

isolator compressibilitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#isolatorCompressibility

The compressibility of the vibration isolator.
has range
float

isolator static deflectiondp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#isolatorStaticDeflection

Static deflection of the vibration isolator. Usually measured in millimeters (mm).
has range
float

lamp ballast typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#lampBallastType

The type of ballast used to stabilise gas discharge by limiting the current during operation and to deliver the necessary striking voltage for starting. Ballasts are needed to operate Discharge Lamps such as Fluorescent, Compact Fluorescent, High-pressure Mercury, Metal Halide and High-pressure Sodium Lamps. Magnetic ballasts are chokes which limit the current passing through a lamp connected in series on the principle of self-induction. The resultant current and power are decisive for the efficient operation of the lamp. A specially designed ballast is required for every type of lamp to comply with lamp rating in terms of Luminous Flux, Color Appearance and service life. The two types of magnetic ballasts for fluorescent lamps are KVG Conventional (EC-A series) and VVG Low-loss ballasts (EC-B series). Low-loss ballasts have a higher efficiency, which means reduced ballast losses and a lower thermal load. Electronic ballasts are used to run fluorescent lamps at high frequencies (approx. 35 - 40 kHz).
has range
string

lamp compensation typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#lampCompensationType

Identifies the form of compensation used for power factor correction and radio suppression.
has range
string

lamp maintenance factordp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#lampMaintenanceFactor

Non recoverable losses of luminous flux of a lamp due to lamp depreciation i.e. the decreasing of light output of a luminaire due to aging and dirt.
has range
float

leakage fully closeddp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#leakageFullyClosed

Leakage when fully closed. Usually measured in m3/s.
has range
float

legenddp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#legend

A text inscribed or applied to the switch as a legend to indicate purpose or function.
has range
string

lengthdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#length

Length of the tubes in the tube bundle. Usually measured in millimeters (mm).
has range
float

lift elevation differencedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#liftElevationDifference

Elevation difference between cooling tower sump and the top of the tower. Usually measured in millimeters (mm).
has range
float

light emitter nominal powerdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#lightEmitterNominalPower

Light emitter nominal power. Usually measured in Watts (W, J/s).
has range
float

limiting terminal sizedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#limitingTerminalSize

The maximum terminal size capacity of the device. Usually measured in square metre (m2).
has range
float

locked rotor currentdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#lockedRotorCurrent

Input current when a motor armature is energized but not rotating. Usually measured in Ampere (A).
has range
float

manual overridedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#manualOverride

Identifies whether hand-operated operation is provided as an override (= TRUE) or not (= FALSE). Note that this value should be set to FALSE by default in the case of a Hand Operated Actuator.
has range
boolean

maximum air flow ratedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#maximumAirFlowRate

Maximum allowable air flow rate. Usually measured in m3/s.
has range
float

maximum apparent powerdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#maximumApparentPower

Maximum apparent power/capacity in VA (volt ampere). Usually measured in Watts (W, J/s).
has range
float

maximum part load ratiodp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#maximumPartLoadRatio

Maximum part load ratio as a fraction of nominal capacity.
has range
float

maximum power outputdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#maximumPowerOutput

The maximum output power rating of the engine. Usually measured in Watts (W, J/s).
has range
float

maximum supported weightdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#maximumSupportedWeight

The maximum weight that can be carried by the vibration isolator. Usually measured in kilograms (kg) or grams (g).
has range
float

maximum working pressuredp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#maximumWorkingPressure

Maximum working pressure. Usually measured in Pascals (Pa, N/m2).
has range
float

mechanical operateddp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#mechanicalOperated

Indication whether the element is operated machanically (TRUE) or not, i.e. manually (FALSE).
has range
boolean

media sourcedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#mediaSource

Indicates media sources and corresponding names of ports (IfcDistributionPort with FlowDirection=SINK and PredefinedType=AUDIOVISUAL) or aggregated audio/video components (IfcAudioVisualAppliance).
has range
string

minimun part load ratiodp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#minimunPartLoadRatio

Minimum part load ratio as a fraction of nominal capacity.
has range
float

motor drive typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#motorDriveType

Motor drive type: DIRECTDRIVE: Direct drive. BELTDRIVE: Belt drive. COUPLING: Coupling. OTHER: Other type of motor drive. UNKNOWN: Unknown motor drive type.
has range
string

motor enclosure typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#motorEnclosureType

A list of the available types of motor enclosure from which that required may be selected.
has range
string

net positive suction headdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#netPositiveSuctionHead

Minimum liquid pressure at the pump inlet to prevent cavitation. Usually measured in Pascals (Pa, N/m2).
has range
float

nominal air flow ratedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalAirFlowRate

Nominal air flow rate. Usually measured in m3/s.
has range
float

nominal body depthdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalBodyDepth

Nominal or quoted =length, measured along the z-axis of the local coordinate system of the object, of the body of the object. Usually measured in millimeters (mm).
has range
float

nominal body lengthdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalBodyLength

Nominal or quoted length, measured along the x-axis of the local coordinate system of the object, of the body of the object. Usually measured in millimeters (mm).
has range
float

nominal body widthdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalBodyWidth

Nominal or quoted length, measured along the y-axis of the local coordinate system of the object, of the body of the object. Usually measured in millimeters (mm).
has range
float

nominal capacitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalCapacity

Compressor nameplate capacity. Usually measured in Watts (W, J/s).
has range
float

nominal capcitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalCapcity

Nominal cooling tower capacity in terms of heat transfer rate of the cooling tower between air stream and water stream at nominal conditions. Usually measured in Watts (W, J/s).
has range
float

nominal condensing temperaturedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalCondensingTemperature

Chiller condensing temperature. Usually measured in degrees Kelvin (K).
has range
float

nominal cooling capacitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalCoolingCapacity

Nominal cooling capacity. Usually measured in Watts (W, J/s).
has range
float

nominal depthdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalDepth

The nominal depth of the tank. Note: Not required for a horizontal cylindrical tank. Usually measured in millimeters (mm).
has range
float

nominal diameterdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalDiameter

Nominal diameter or width of the tubes in the tube bundle. Usually measured in millimeters (mm).
has range
float

nominal efficiencydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalEfficiency

Nominal chiller efficiency under nominal conditions.
has range
float

nominal energy consumptiondp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalEnergyConsumption

Nominal fuel consumption rate required to produce the total boiler heat output. Usually measured in Watts (W, J/s).
has range
float

nominal evaporating temmperaturedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalEvaporatingTemmperature

Chiller evaporating temperature.Usually measured in degrees Kelvin (K).
has range
float

nominal filter face velocitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalFilterFaceVelocity

Filter face velocity. Usually measured in m/s.
has range
float

nominal flow ratedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalFlowRate

Nominal fluid flow rate through the filter. Usually measured in m3/s.
has range
float

nominal frequencydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalFrequency

The nominal frequency of the supply. Usually measured in cycles/s or Hertz (Hz).
has range
float

nominal heat rejection ratedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalHeatRejectionRate

Sum of the refrigeration effect and the heat equivalent of the power input to the compressor. Usually measured in Watts (W, J/s).
has range
float

nominal heat transfer areadp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalHeatTransferArea

Nominal heat transfer surface area associated with nominal overall heat transfer coefficient. Usually measured in square metre (m2).
has range
float

nominal heat transfer coefficientdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalHeatTransferCoefficient

Nominal overall heat transfer coefficient associated with nominal heat transfer area. Usually measured in Watts/m2 Kelvin.
has range
float

nominal heating capacitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalHeatingCapacity

Nominal heating capacity. Usually measured in Watts (W, J/s).
has range
float

nominal latent capacitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalLatentCapacity

Nominal latent capacity. Usually measured in Watts (W, J/s).
has range
float

nominal length or diameterdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalLengthOrDiameter

The nominal length or, in the case of a vertical cylindrical tank, the nominal diameter of the tank. Usually measured in millimeters (mm).
has range
float

nominal media surface velocitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalMediaSurfaceVelocity

Average fluid velocity at the media surface. Usually measured in m/s.
has range
float

nominal moisture gaindp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalMoistureGain

Nominal rate of water vapor added into the airstream. Usually measured in kg/s.
has range
float

nominal part load ratiodp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalPartLoadRatio

Allowable part load ratio range.
has range
real real range c

nominal particle geometric mean diameterdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalParticleGeometricMeanDiameter

Particle geometric mean diameter associated with nominal efficiency. Usually measured in millimeters (mm).
has range
float

nominal particle geometric standard deviationdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalParticleGeometricStandardDeviation

Particle geometric standard deviation associated with nominal efficiency.
has range
float

nominal power consumptiondp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalPowerConsumption

Nominal total power consumption. Usually measured in Watts (W, J/s).
has range
float

nominal power ratedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalPowerRate

Nominal fan power rate.Usually measured in Watts (W, J/s).
has range
float

nominal pressure dropdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalPressureDrop

Total pressure drop across the filter. Usually measured in Pascals (Pa, N/m2).
has range
float

nominal return water temperature coolingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalReturnWaterTemperatureCooling

Nominal return water temperature (refers to nominal cooling capacity). Usually measured in degrees Kelvin (K).
has range
float

nominal return water temperature heatingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalReturnWaterTemperatureHeating

Nominal return water temperature (refers to nominal heating capacity). Usually measured in degrees Kelvin (K).
has range
float

nominal rotation speeddp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalRotationSpeed

Nominal fan wheel speed. Usually measured in cycles/s.
has range
float

nominal sensible capacitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalSensibleCapacity

Nominal sensible capacity. Usually measured in Watts (W, J/s).
has range
float

nominal sorrounding humidity coolingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalSorroundingHumidityCooling

Nominal surrounding humidity (refers to nominal cooling capacity). Usually measured in degrees Kelvin (K).
has range
float

nominal sorrounding temperature coolingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalSorroundingTemperatureCooling

Nominal surrounding temperature (refers to nominal cooling capacity). Usually measured in degrees Kelvin (K).
has range
float

nominal sorrounding temperature heatingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalSorroundingTemperatureHeating

Nominal surrounding temperature (refers to nominal heating capacity). Usually measured in degrees Kelvin (K).
has range
float

nominal static pressuredp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalStaticPressure

The static pressure within the air stream that the fan must overcome to insure designed circulation of air. Usually measured in Pascals (Pa, N/m2).
has range
float

nominal supply voltagedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalSupplyVoltage

The nominal voltage of the supply. Usually measured in Volts (V, W/A).
has range
float

nominal supply voltage offsetdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalSupplyVoltageOffset

The maximum and minimum allowed voltage of the supply e.g. boundaries of 380V/440V may be applied for a nominal voltage of 400V.
has range
real real range c

nominal supply water temperature coolingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalSupplyWaterTemperatureCooling

Nominal supply water temperature (refers to nominal cooling capacity). Usually measured in degrees Kelvin (K).
has range
float

nominal supply water temperature heatingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalSupplyWaterTemperatureHeating

Nominal supply water temperature (refers to nominal heating capacity). Usually measured in degrees Kelvin (K).
has range
float

nominal total pressuredp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalTotalPressure

Nominal total pressure rise across the fan. Usually measured in Pascals (Pa, N/m2).
has range
float

nominal uadp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalUa

Nominal UA value.
has range
float

nominal water flow coolingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalWaterFlowCooling

Nominal water flow (refers to nominal cooling capacity). Usually measured in m3/s.
has range
float

nominal water flow heatingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalWaterFlowHeating

Nominal water flow (refers to nominal heating capacity). Usually measured in m3/s.
has range
float

nominal width or diameterdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nominalWidthOrDiameter

The nominal width or, in the case of a horizontal cylindrical tank, the nominal diameter of the tank. Note: Not required for a vertical cylindrical tank. Usually measured in millimeters (mm).
has range
float

nomminal rotation speeddp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#nomminalRotationSpeed

Pump rotational speed under nominal conditions. Usually measured in cycles/s.
has range
float

number of bladesdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#numberOfBlades

Number of blades.
has range
integer

number of cellsdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#numberOfCells

Number of cells in one cooling tower unit.
has range
integer

number of circuitsdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#numberOfCircuits

Number of parallel fluid tube circuits.
has range
integer

number of gangsdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#numberOfGangs

Number of gangs/buttons on this switch.
has range
integer

number of panelsdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#numberOfPanels

Number of panels.
has range
integer

number of rowsdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#numberOfRows

Number of tube rows in the tube bundle assembly.
has range
integer

number of sectionsdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#numberOfSections

Number of sections used in the construction of the tank. Default is 1. Note: All sections assumed to be the same size.
has range
integer

number os socketsdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#numberOsSockets

The number of sockets that may be connected. In case of inconsistency, sockets defined on ports take precedence.
has range
integer

open pressure dropdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#openPressureDrop

Total pressure drop across damper. Usually measured in Pascals (Pa, N/m2).
has range
float

operating modedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#operatingMode

Identifies the operating mode of the boiler.
has range
string

operating wightdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#operatingWight

Operating weight of the tank including all of its contents. Usually measured in kilograms (kg) or grams (g).
has range
float

operationdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#operation

The operational mechanism for the damper operation.
has range
string

operation temperature rangedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#operationTemperatureRange

Allowable operation ambient air temperature range. Usually measured in degrees Kelvin (K).
has range
float
real real range c

operational riterialdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#operationalRiterial

Time of operation at maximum operational ambient air temperature. Measured in seconds (s) or days (d) or other units of time.
has range
float

operational temperature rangedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#operationalTemperatureRange

Allowable operation ambient air temperature range. Usually measured in degrees Kelvin (K).
has range
real real range c

orientationdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#orientation

The intended orientation for the damper as specified by the manufacturer.
has range
string

outlet connection sizedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#outletConnectionSize

Size of the outlet connection. Usually measured in millimeters (mm).
has range
float

outlet temperature rangedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#outletTemperatureRange

Allowable outlet temperature of either the water or the steam. Usually measured in degrees Kelvin (K).
has range
real real range c

output capacitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#outputCapacity

Total nominal heat output as listed by the manufacturer. Usually measured in Watts (W, J/s).
has range
float

outside diameterdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#outsideDiameter

Actual outside diameter of the tube in the tube bundle. Usually measured in millimeters (mm).
has range
float

pattern typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#patternType

Defines the types of pattern (or shape of a tank that may be specified.
has range
string

pipe connection enumdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#pipeConnectionEnum

The manner in which the pipe connection is made to the cooled beam.
has range
string

placement typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#placementType

Indicates the placement of the coil. FLOOR indicates an under floor heater (if coil type is WATERHEATINGCOIL or ELECTRICHEATINGCOIL), CEILING indicates a cooling ceiling (if coil type is WATERCOOLINGCOIL), UNIT indicates that the coil is part of a cooling or heating unit, like cooled beam, etc.
has range
string

power sourcedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#powerSource

Type of power driving the compressor.
has range
string

pressure ratingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#pressureRating

Nominal pressure rating of the boiler as rated by the agency having jurisdiction. Usually measured in Pascals (Pa, N/m2).
has range
float

primary air flow rate rangedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#primaryAirFlowRateRange

possible range of primary airflow that can be delivered. Usually measured in m3/s.
has range
real real range c

primary apparent powerdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#primaryApparentPower

The power in VA (volt ampere) that has been transformed and that runs into the transformer on the primary side. Usually measured in Watts (W, J/s).
has range
float

primary currentdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#primaryCurrent

The current that is going to be transformed and that runs into the transformer on the primary side. Usually measured in Ampere (A).
has range
float

primary frequencydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#primaryFrequency

The frequency that is going to be transformed and that runs into the transformer on the primary side. Usually measured in cycles/s or Hertz (Hz).
has range
float

primary voltagedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#primaryVoltage

The voltage that is going to be transformed and that runs into the transformer on the primary side. Usually measured in Volts (V, W/A).
has range
float

read out typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#readOutType

Indication of the form that readout from the meter takes. In the case of a dial read out, this may comprise multiple dials that give a cumulative reading and/or a mechanical odometer.
has range
string

real impedance ratiodp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#realImpedanceRatio

The ratio between the real part of the zero sequence impedance and the real part of the positive impedance (i.e. real part of the short-circuit voltage) of the transformer. Used for three-phase transformer which includes a N-conductor.
has range
float

refrigerant classdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#refrigerantClass

Refrigerant class used by the compressor. CFC: Chlorofluorocarbons. HCFC: Hydrochlorofluorocarbons. HFC: Hydrofluorocarbons.
has range
string

remote readingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#remoteReading

Indicates whether the meter has a connection for remote reading through connection of a communication device (set TRUE) or not (set FALSE).
has range
boolean

roughnessdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#roughness

A measure of the vertical deviations of the surface.
has range
string

second curvature radiusdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#secondCurvatureRadius

SecondCurvatureRadius should be defined as the top or right side radius of curvature value. Usually measured in millimeters (mm).
has range
float

secondary air flow rate rangedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#secondaryAirFlowRateRange

possible range of secondary airflow that can be delivered. Usually measured in Pascals (Pa, N/m2).
has range
real real range c

secondary apparent powerdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#secondaryApparentPower

The power in VA (volt ampere) that has been transformed and is running out of the transformer on the secondary side. Usually measured in Watts (W, J/s).
has range
float

secondary currentdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#secondaryCurrent

The current that has been transformed and is running out of the transformer on the secondary side. Usually measured in Ampere (A).
has range
float

secondary current typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#secondaryCurrentType

A list of the secondary current types that can result from transformer output.
has range
string

secondary frequencydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#secondaryFrequency

The frequency that has been transformed and is running out of the transformer on the secondary side. Usually measured in cycles/s or Hertz (Hz).
has range
float

secondary voltagedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#secondaryVoltage

The voltage that has been transformed and is running out of the transformer on the secondary side. Usually measured in Volts (V, W/A).
has range
float

shading device typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#shadingDeviceType

Specifies the type of shading device.
has range
string

short circuit voltageop back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#shortCircuitVoltage

A complex number that specifies the real and imaginary parts of the short-circuit voltage at rated current of a transformer given in %.
is also defined as
object property

sizedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#size

The size of the connection to the valve (or to each connection for faucets, mixing valves, etc.). Usually measured in millimeters (mm).
has range
float

solar reflectancedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#solarReflectance

(Rsol): The ratio of incident solar radiation that is reflected by a shading system (also named _e). Note the following equation Asol + Rsol + Tsol = 1
has range
float

solar transmittancedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#solarTransmittance

(Tsol) The ratio of incident solar radiation that directly passes through a shading system (also named _e). Note the following equation Asol + Rsol + Tsol = 1
has range
float

spectrumdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#spectrum

The spectrum of radiation describes its composition with regard to wavelength. Light, for example, as the portion of electromagnetic radiation that is visible to the human eye, is radiation with wavelengths in the range of approx. 380 to 780 nm (1 nm = 10 m). The corresponding range of colours varies from violet to indigo, blue, green, yellow, orange, and red. These colours form a continuous spectrum, in which the various spectral sectors merge into each other.
has range
real real range c

spray typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#sprayType

SprayFilled: Water is sprayed into airflow. SplashTypeFill: water cascades over successive rows of splash bars. FilmTypeFill: water flows in a thin layer over closely spaced sheets.
has range
string

staggered row spacingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#staggeredRowSpacing

Staggered tube row spacing. Usually measured in millimeters (mm).
has range
float

standarddp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#standard

the designation of the Standard applicable for the definition of the characteristics of the tripping_unit.
has range
string

start current factordp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#startCurrentFactor

IEC. Start current factor defines how large the peek starting current will become on the engine. StartCurrentFactor is multiplied to NominalCurrent and we get the start current.
has range
float

starting timedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#startingTime

The time (in s) needed for the motor to reach its rated speed with its driven equipment attached, starting from standstill and at the nominal voltage applied at its terminals.
has range
float

storage typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#storageType

Defines the general material category intended to be stored.
has range
string

switch functiondp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#switchFunction

Indicates types of switches which differs in functionality.
has range
string

te timedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#teTime

The maximum time (in s) at which the motor could run with locked rotor when the motor is used in an EX-environment. The time indicates that a protective device should trip before this time when the starting current of the motor is slowing through the device.
has range
float

temperature classificationdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#temperatureClassification

Enumeration defining the temperature classification of the space heater surface temperature. low temperature - surface temperature is relatively low, usually heated by hot water or electricity. high temperature - surface temperature is relatively high, usually heated by gas or steam.
has range
string

temperature rangedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#temperatureRange

Allowable minimum and maximum temperature. Usually measured in degrees Kelvin (K).
has range
real real range c

temperature ratingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#temperatureRating

Temperature rating. Usually measured in degrees Kelvin (K).
has range
float

test pressuredp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#testPressure

The maximum pressure to which the valve has been subjected under test. Usually measured in Pascals (Pa, N/m2).
has range
float

thermal conductivitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#thermalConductivity

Fouling factor of the tubes in the tube bundle. Usually measured in m2 Kelvin/Watt.
has range
float

thermal efficiencydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#thermalEfficiency

Overall Thermal Efficiency is defined as gross energy output of the heat transfer device divided by the energy input.
has range
float

thermal mass heat capacitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#thermalMassHeatCapacity

Product of component mass and specific heat.
has range
float

thermal transmittancedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#thermalTransmittance

IfcThermalTransmittanceMeasure is a measure of the rate at which energy is transmitted through a body. Usually measured in Watts/m2 Kelvin.
has range
float

transformer vector groupdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#transformerVectorGroup

List of the possible vector groups for the transformer from which that required may be set. Values in the enumeration list follow a standard international code where the first letter describes how the primary windings are connected, the second letter describes how the secondary windings are connected, and the numbers describe the rotation of voltages and currents from the primary to the secondary side in multiples of 30 degrees. D: means that the windings are delta-connected. Y: means that the windings are star-connected. Z: means that the windings are zig-zag connected (a special start-connected providing low reactance of the transformer). The connectivity is only relevant for three-phase transformers.
has range
string

valve mechanismdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#valveMechanism

The mechanism by which the valve function is achieved where: BALL: Valve that has a ported ball that can be turned relative to the body seat ports. BUTTERFLY: Valve in which a streamlined disc pivots about a diametric axis. CONFIGUREDGATE: Screwdown valve in which the closing gate is shaped in a configured manner to have a more precise control of pressure and flow change across the valve. GLAND: Valve with a tapered seating, in which a rotatable plug is retained by means of a gland and gland packing. GLOBE: Screwdown valve that has a spherical body. LUBRICATEDPLUG: Plug valve in which a lubricant is injected under pressure between the plug face and the body. NEEDLE: Valve for regulating the flow in or from a pipe, in which a slender cone moves along the axis of flow to close against a fixed conical seat. PARALLELSLIDE: Screwdown valve that has a machined plate that slides in formed grooves to form a seal. PLUG: Valve that has a ported plug that can be turned relative to the body seat ports. WEDGEGATE: Screwdown valve that has a wedge shaped plate fitting into tapered guides to form a seal.
has range
string

valve operationdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#valveOperation

The method of valve operation where: DROPWEIGHT: A valve that is closed by the action of a weighted lever being released, the weight normally being prevented from dropping by being held by a wire, the closure normally being made by the action of heat on a fusible link in the wire FLOAT: A valve that is opened and closed by the action of a float that rises and falls with water level. The float may be a ball attached to a lever or other mechanism HYDRAULIC: A valve that is opened and closed by hydraulic actuation LEVER: A valve that is opened and closed by the action of a lever rotating the gate within the valve. LOCKSHIELD: A valve that requires the use of a special lockshield key for opening and closing, the operating mechanism being protected by a shroud during normal operation. MOTORIZED: A valve that is opened and closed by the action of an electric motor on an actuator PNEUMATIC: A valve that is opened and closed by pneumatic actuation SOLENOID: A valve that is normally held open by a magnetic field in a coil acting on the gate but that is closed immediately if the electrical current generating the magnetic field is removed. SPRING: A valve that is normally held in position by the pressure of a spring on a plate but that may be caused to open if the pressure of the fluid is sufficient to overcome the spring pressure. THERMOSTATIC: A valve in which the ports are opened or closed to maintain a required predetermined temperature. WHEEL: A valve that is opened and closed by the action of a wheel moving the gate within the valve.
has range
string

valve patterndp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#valvePattern

The configuration of the ports of a valve according to either the linear route taken by a fluid flowing through the valve or by the number of ports where: SINGLEPORT: Valve that has a single entry port from the system that it serves, the exit port being to the surrounding environment. ANGLED_2_PORT: Valve in which the direction of flow is changed through 90 degrees. STRAIGHT_2_PORT: Valve in which the flow is straight through. STRAIGHT_3_PORT: Valve with three separate ports. CROSSOVER_4_PORT: Valve with 4 separate ports.
has range
string

ventilating pipe sizedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#ventilatingPipeSize

Size of the ventilating pipe(s). Usually measured in millimeters (mm).
has range
float

vertical spacingdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#verticalSpacing

Vertical spacing between tubes in the tube bundle.Usually measured in millimeters (mm).
has range
float

vibration transmissibilitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#vibrationTransmissibility

the vibration transmissibility percentage.
has range
float

visible light reflectancedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#visibleLightReflectance

Fraction of the visible light that is reflected by the glazing at normal incidence. It is a value without unit.
has range
float

visible light transmittancedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#visibleLightTransmittance

Fraction of the visible light that passes the shading system at normal incidence. It is a value without unit.
has range
float

volumendp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#volumen

Total volume of fluid in the tubes and their headers. Usually measured in cubic metre (m3).
has range
float

water flow control system typedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#waterFlowControlSystemType

Factory fitted waterflow control system.
has range
string

water inlet temperature rangedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#waterInletTemperatureRange

Allowable water inlet temperature range. Usually measured in degrees Kelvin (K).
has range
real real range c

water pressure rangedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#waterPressureRange

Allowable water circuit working pressure range. Usually measured in Pascals (Pa, N/m2).
has range
real real range c

water requirementdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#waterRequirement

Make-up water requirement. Usually measured in m3/s.
has range
float

water storage capacitydp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#waterStorageCapacity

Water storage capacity. Usually measured in cubic metre (m3).
has range
float

weightdp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#weight

The weight of the humidifier. Usually measured in kilograms (kg) or grams (g).
has range
float

working pressuredp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#workingPressure

The normally expected maximum working pressure of the valve. Usually measured in Pascals (Pa, N/m2).
has range
float

working pressure rangedp back to ToC or Data Property ToC

IRI: http://saref.linkeddata.es/def/bldg#workingPressureRange

Allowable minimum and maximum working pressure (relative to ambient pressure). Usually measured in Pascals (Pa, N/m2).
has range
real real range c